Short circuit current rating for PVC & XLPE cables

Short Circuit Rating are based on the assumption that duration of the short circuit is to small and apparently that there is no transmission of heat, produced during short circuit, through the insulation and the whole of it is absorbed by the conductor. With a high increase in KVA, capacity in power distribution system, cables are expected to carry short circuit to carry short circuit current of high magnitude. Normally rated at 70 C,PVC insulation material permit a short circuit temperature of160 C.

T: Duration of Short Circuit in seconds.

A: Area of Conductor in Sq.mm.

K: Constant

For Copper with general purpose PVC Insulation- 0.115

For Copper with Heat Resisting PVC Insulation- 0.104

For Copper with XLPE Insulation- 0.143

Short Circuit Current rating

Nom.
Cross
 Sectional
Area

For General purpose PVC Insulation

For Heat resist PVC Insulation

For XLPE Insulation

(mm2)

KA

KA

KA

1.5

0.156

0.173

0.2145

2.5

0.26

0.288

0.3575

4

0.416

0.460

0.572

6

0.624

0.690

0.858

10

1.04

1.150

1.43

16

1.664

1.840

2.288

25

2.6

2.875

3.575

35

3.64

4.025

5.005

50

5.2

5.750

7.15

70

7.28

8.050

10.01

95

9.88

10.925

13.585

120

12.48

13.800

17.16

150

15.6

17.250

21.45

185

19.24

21.275

26.455

240

24.96

27.600

34.32

300

31.2

34.500

42.9